Mastervolt XS 2000 AC Grid Tie inverter 1500 Watt

Mastervolt XS 2000 AC Grid Tie inverter 1500 Watt
 
Art.No.:PD-01339
Weight:10,00 kg
Manufacturer:Mastervolt
Delivery time: Directly delivering

 
Including VAT (19%)
excl. Transport surcharge

 Piece Add to cart
Specification

 
GENERAL
Operating temperature -20 to 60 °C, full power up to 45 °C ambient air temperature, derating -3%/°C acove 45 °C
Relative humidity maximum 95% non-condensing; PCB has anti-moisture coating
Protection degree IP44
Safety class class I (metal housing with earth connection)
Galvanic isolation yes (safety transformer)
Dimensions (HxWxD) 545x356x145 mm
Weight 10 kg
Product warranty 5 year
 
SOLAR INPUT (DC)
Recommended PV power range 1300 - 2000 Wp
Nominal input power 1590 W DC
Maximum input power 1670 W DC
Start-up power 5 W
Operating voltage range 100 - 450 V DC
MPP voltage range at nom. power 145 - 360 V DC
Maximum voltage 450 V DC
Number of inputs 2 string connections each are connected in parallel
Rated current 11 A
MPP tracker 1 MPP tracker
MPP efficiency 99,9% (Fraunhofer algorithm)
DC connection 2 sets of MultiContact (4 mm) connectors
 
GRID OUTPUT (AC)
Voltage 230 V AC single phase (184 - 265 V, country dependent)
Nominal output power at 45 °C 1500 W
Maximum output power 1575 W
Nominal current 8 A
Frequency 45 - 65 Hz, country dependent
Power factor > 0.99 at full power
Harmonic distortion (THD) < 3% at full power
Standby power < 0.5 W
European efficiency 94.4% at 300 V
Maximum efficiency 95.7%
AC connection 2.5 - 4 mm² terminal block
Fuse internal PCB fuse
 
MONITORING
User interface integrated LCD - display with backlight, 4 buttons and bright diagnostic LED. All relevant AC and DC values plus diagnostic messages
External communication 2 surge protected RS485 connections. 2 Masterbus connections. Max. 20 XS units can be connected to 1 Data Control Pro datalogger
 
SAFETY REGULATIONS
General galvanic seperation between DC and AC side by means of a HF safety transformer
Island protection redundant voltage and frequency window monitoring. Independent cut-off by means of 2-pole relay and solid state switch according to VDE V 0126-1-1:2006
Temperature protection thermal switch-off at internal over temperature
Safety devices DC side isolation resistance monitoring • overvoltage detection • inverse polarity protection • current limitation • transients / surges (varistors) • overload protection
Safety devices AC side current limitation • DC injection protection • short circuit protection (ceramic fuse) • over-/undervoltage and over-/underfrequency monitoring • active anti-islanding algorithm
DC current injection VDE0126-1-1 / DK5940 / G83 / KSC8536 compliant
 
REGULATIONS AND DIRECTIVES
CE conformity yes
EMC directive 89/336/EEC
Emission EN 55022, class B
Harmonics EN 61000-3-2
Dips, variations, flicker EN 61000-4-11 and -3-3
Immunity EN 55024; EN 61000-4-2 and -3; EN 61000-4-4, -4-5 and -4-6
LV directive 2006/95/EC
Electrical safety EN 60950-1
National grid interface req. VDE 0126-1-1 / DK5940 / RD1663-2000 / K SC 8536 / G83-1 compliant